85
  Default Trip Limits and Times According to IEEE1547

Default Trip Limits and Times According to IEEE1547

NOTE
The inverters are equipped with adjustable utility protective function set-
points, and can be aggregated above 30kW on a single Point of Common
Connection. The default settings are in compliance with IEEE1547. Utility
authorization is required to change these set-points.
Voltage Range (% of Base Voltage) Maximum Clearing Time (Sec)
V < 50%
50 % < V < 88%
110% < V < 120%
V > 120 %
Frequency Range (Hz)
> 60.5
< 59.3 (Hawaii – 57)

Recommended OCPD Size per Grid

Inverter
SE5000H-AU
 
  Maximum Output
Current (A)
21
EV Charging Single Phase Inverter MAN-01-00629-1.2
0.16
2.00
1.00
0.16
Maximum Clearing Time (Sec)
0.16
0.16
Minimum Fuse Rating
(A)
30
  Maximum Fuse
Rating (A)
50