Default Trip Limits and Times According to IEEE1547
NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on
a single Point of Common Connection. The default settings are in compliance with IEEE1547. Utility authorization is
required to change these set-points.
(1) Time accuracy is +-30ms
Voltage Range (% of Base Voltage) Maximum Clearing Time (Sec)
V < 50%
50 % < V < 88%
110% < V < 120%
V > 120 %
Frequency Range (Hz)
> 60.5
< 59.3 (Hawaii – 57)
SolarEdge-Single Phase Inverter with HD-Wave Technology Installation MAN-01-00541-1.4
0.16
2.00
1.00
0.16
Maximum Clearing Time (Sec)
0.16
0.16
(1)
(1)