Default Trip Limits And Times According To Ieee1547 - SolarEdge UL1741-SA Installation Manual

Single phase inverter with hdwave technology with setapp configuration
Table of Contents

Advertisement

79

Default Trip Limits and Times According to IEEE1547

NOTE
The inverters are equipped with adjustable utility protective function set-points, and can be aggregated above 30kW on
a single Point of Common Connection. The default settings are in compliance with IEEE1547. Utility authorization is
required to change these set-points.
(1) Time accuracy is +-30ms
Voltage Range (% of Base Voltage) Maximum Clearing Time (Sec)
V < 50%
50 % < V < 88%
110% < V < 120%
V > 120 %
Frequency Range (Hz)
> 60.5
< 59.3 (Hawaii – 57)
SolarEdge-Single Phase Inverter with HD-Wave Technology Installation MAN-01-00541-1.4
0.16
2.00
1.00
0.16
Maximum Clearing Time (Sec)
0.16
0.16
(1)
(1)