Open the AC cable gland and insert the cable through the AC gland.
 4.
WARNING!
Turn OFF the AC before connecting the AC terminals. If connecting
equipment grounding wire, connect it before connecting the AC Line and
Neutral wires.
 5. Connect the AC wires according to the labels on the terminal block.
Connection Unit with Safety Switch
Wire type
PE (grounding)
Line
Neutral
 6. Check that the wires are fully inserted and cannot be pulled out easily.
 7. Tighten the AC cable gland with a torque of 2.8-3.3 N*m
 8. Verify that there are no unconnected wires to the inverter and that the unused
terminal screws are tightened.
To connect additional grounding:
 1. Repeat steps 1- 3 from the previous procedure.
 2. Open the AC cable gland and insert the grounding cable through the AC gland.
 3. Strip 8mm of the grounding wire insulation (see Figure 15 ).
EV Charging Single Phase Inverter MAN-01-00629-1.2
Chapter 4: Connecting the AC and the Strings to the Connection Unit
Connect to
terminal
GND
L
N
 
Figure 16: Connection Unit AC Terminals
 
    32