Connecting the Strings to the Connection Unit with Safety Switch
NOTE
SolarEdge's fixed input voltage architecture enables the parallel strings to be of
different lengths. Therefore, they do not need to have the same number of
power optimisers, as long as the length of each string is within the permitted
range.
4. Close the Connection Unit with Safety Switch cover: Attach the switch cover and
secure it by tightening the four screws with a torque of 1.2 N*m/ 0.9 lb*ft.
5. Ensure proper conduit sealing; inspect the entire conduit run and use standard
conduit sealants to avoid water penetration.