Dexter Laundry B Series Operators Manual Installation & Operation Instructions page 14

Industrial, on-premise control, electric-heated
Hide thumbs Also See for B Series:
Table of Contents

Advertisement

T-20X2 MODELS:
HEATING
SUPPLY VOLTAGE
ELEMENT SIZE
(kW)
15
3 / 208 / 60 hz
15
3 / 240 / 60 hz
16
1 / 208 / 60 hz
16
1 / 240 / 60 hz
15
3 / 400 / 50 hz
T-30X2 MODELS:
HEATING
SUPPLY VOLTAGE
ELEMENT SIZE
(kW)
20
20
24
24
For 240V power supplies, an earthed mid-point of a phase is required. The "high" leg of the 3-phase
electrical supply (delta) must be connected to terminal L3. A neutral is required for all electrical supply
variations, see the wiring diagram affixed to the belt guard on the back of the dryer.
The installation must meet the electrical requirements of the country, state and locality of the installation.
The installer may be required to provide a disconnect switch which will interrupt all lines. It may be a
local or national requirement to provide an electrical interruption switch visible and accessible from the
room in which the dryer is installed. The wiring diagram is located on the belt guard on the back of the
dryer.
8514-265-001 REV C PAGE 14
MINIMUM DUAL ELEMENT
(
)
TIME DELAY FUSE SIZE AT
PHASE / V.
FUSED DISCONNECT (A.)
MINIMUM DUAL ELEMENT
(PHASE / V.)
TIME DELAY FUSE SIZE AT
FUSED DISCONNECT (A.)
1 / 208
1 / 240
3 / 208
3 / 240
MINIMUM WIRE SIZE FROM FUSED
DISCONNECT TO DRYER TERMINAL
BLOCK (75
60
50
100
90
30
MINIMUM WIRE SIZE FROM FUSED
DISCONNECT TO DRYER TERMINAL
BLOCK (75
125
110
90
80
O
C COPPER WIRE)
#4
#4
#1
#2
8.4 mm2
O
C COPPER WIRE)
(1/0)
(1/0)
# 2
# 3