Huawei UPS5000-S-600 User Manual page 57

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
The specifications listed in the following table are measured at a rated voltage of 380 V.
Table 3-4 Recommended upstream input and downstream output circuit breakers
UPS Capacity
50 kVA
100 kVA
150 kVA
200 kVA
250 kVA
300 kVA
350 kVA
400 kVA
Issue 05 (2019-12-20)
Routing mode: Routing the cables over the cable ladder or bracket in a single layer
(IEC60364-5-52 middle E). The distances between cables must be greater than
twice the cable diameter.
The ambient temperature is 30° C.
The AC voltage loss is less than 3%, and the DC voltage loss is less than 1%.
90° C copper flexible cable.
The length of the AC power cables of a UPS is no longer than 30 m and DC power
cables no longer than 50 m.
Component
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Output branch circuit breaker
Mains input circuit breaker
Bypass input circuit breaker
Copyright © Huawei Technologies Co., Ltd.
3 Installation
Specifications
160 A/3P
100 A/3P
100 A/3P
250 A/3P
160 A/3P
160 A/3P
320 A/3P
250 A/3P
250 A/3P
400 A/3P
400 A/3P
400 A/3P
630 A/3P
400 A/3P
400 A/3P
630 A/3P
630 A/3P
630 A/3P
800 A/3P
630 A/3P
630 A/3P
800 A/3P
630 A/3P
49