UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Alarm ID
Alarm Name
(Alarm
ID-Cause
ID)
0036-2
Battery
maintenance
reminder
Battery
0037-1
undervoltage
0040-7
Rectifier abnormal
0043-1
Fan abnormal
0043-2
0043-3
0043-4
0047-1
Not ready
0060-4
Inverter abnormal
Issue 05 (2019-12-20)
Severity
Cause
meet
requirements.
Warning
The time for
maintenance arrives.
The UPS has
Critical
worked in battery
mode for an
extended amount
of time.
The charger is
faulty.
The fan for the
Critical
power module is
not functioning
properly.
The air channel
for the power
module is
obstructed.
Critical
The fan for the
power module is
abnormal.
The fan
monitoring cable
for the power
module is not
working
properly.
The fan is faulty.
The fan is faulty.
The fan
monitoring cable
is faulty.
The ready switch is
Critical
OFF.
Critical
A load
short-circuit
occurs.
Copyright © Huawei Technologies Co., Ltd.
A Alarm List
Solution
Maintain the batteries.
1. Check whether the battery
voltage is normal.
2. Check whether the output is
overloaded.
3. Check whether any battery is
damaged. If yes, replace the
battery.
4. Check whether any battery
charger generates an alarm. If
yes, replace the faulty module.
1. Check that the air channel for
the module is free from
blockage.
2. Check whether the fans are
functioning properly. Replace
the power module if the fans
are faulty.
Replace the faulty power module.
Check the fan or replace the
bypass module.
1. Replace the fan.
2. Check the fan monitoring
cable.
Close the ready switch.
1. Check load cable distributions.
2. If load cable distributions are
normal, replace the power
197