Huawei UPS5000-S-600 User Manual page 200

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Item
Output power factor
Transfer time
Output voltage
imbalance
Overload capability
Table 8-8 System electrical specifications
Item
Redundancy design
ECO
Issue 05 (2019-12-20)
Specifications
voltage)
1
Uninterruptible transfer: 0 ms
Interruptible transfer: ≤ 20 ms
Voltage imbalance: ± 3%; phase imbalance: 120± 2°
Inverter overload capability:
105% < load ≤ 110%: transfer to bypass mode after 60
minutes
110% < load ≤ 125%: transfer to bypass mode after 10
minutes
125% < load ≤ 150%: transfer to bypass mode after 1 minute
Load > 150% or a short circuit occurs: run for 200 ms
Specifications
The auxiliary power supplies, centralized controllers, and
parallel signals use redundancy design.
Supported
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
192