UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Item
Bus Capa. Life
Paral. sys.
hibernate
Hibernated
redundant
modules
Module cycle
hiber. period
(d)
D.G. ECO
Bypass Supply
RAM
verification
Record time
after fault
Collect
real-time site
waveform
Table 4-7 Input Setting
Item
Issue 05 (2019-12-20)
Description
If this parameter is set to Enable, the UPS
detects the bus capacitor lifespan.
When customer loads are light, enable parallel
hibernation to alternate modules in hibernation
mode, which can prolong their service life and
improve the system efficiency.
Redundant modules required for hibernation.
Indicates the rotation interval of modules in
hibernation mode. The default value is 30,
which means that the hibernating module is
rotated every 30 days.
Indicates whether ECO bypass is allowed to
supply power in D.G. mode. When the D.G. is
connected to the dry contact signal GEN:
If this parameter is set to Enable, the system
can enter ECO bypass mode when the D.G.
supplies power to the bypass and the ECO
function is enabled.
If this parameter is set to Disable, the
system is not allowed to enter ECO mode
when the D.G. supplies power to the bypass.
Enable or disable the memory check function.
If this parameter is set to Enable, the control
chip RAM working status is checked regularly.
If this parameter is set to Disable, regular check
is disabled.
Indicates the time for storing fault data after the
UPS experiences a fault. The default value is 0
ms, which means that the data during 20 ms
before the fault occurs is recorded. If the value
is set to 40 ms, it means that the data during 20
ms before the fault occurs and the data during
40 ms after the fault occurs are recorded, and
the like.
If this parameter is set to Enable, one
waveform can be stored manually.
Description
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value
Value
Range
Disable
Disable,
Enable
Disable
Disable,
Enable
1
0–19
30
1–100
Enable
Disable,
Enable
Disable
Disable,
Enable
0 ms, 20
0 ms
ms, 40
ms, 60
ms, 80 ms
Disable
Disable,
Enable
Default
Value
Value
Range
139