Huawei UPS5000-S-600 User Manual page 125

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Figure 4-39 Battery Settings 2
Figure 4-40 Battery Settings 3
Item
Battery
type
Single
battery
voltage (V)
Single
battery
capacity
(Ah)
Batteries in
a battery
string
Issue 05 (2019-12-20)
Description
Set the battery type based on actual
conditions. Currently, only lead-acid
batteries are supported.
Specifies the voltage of each battery
that is connected in the battery string
in series.
Specifies the capacity of each battery
that is connected in the battery string
in series.
Specifies the number of batteries in a
battery string.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value Range
Value
N/A
N/A
12
2, 6, 12
600
5–9999
2 V
2 V battery:
battery:
180–300
240
6 V battery:
6 V
60–100
battery: 80
12 V battery:
117