UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Figure 4-32 System Settings 1
Item
Single/Parallel
Requisite
modules
Redundant
modules
Working
mode
ECO voltage
range
BSC mode
Issue 05 (2019-12-20)
Description
Specifies whether the UPS works in single
mode or parallel mode.
Matches the system capacity.
Set this parameter according to load capacity
and redundancy requirements.
UPS working mode.
In ECO mode, when the difference between
the bypass voltage and the rated voltage is
greater than this value, the system determines
that the ECO voltage is abnormal and
transfers to normal mode.
If the system is a dual-bus system that
consists of Huawei UPSs, set this
parameter to Standard BSC mode.
A dual-bus system consists of the master
and slave BSC systems. You can specify
the master and slave BSC systems (one
master and one slave) and change the
settings under the guidance of
maintenance engineers. Set the master and
slave BSC systems to master and slave
BSC modes respectively.
Ensure that the BSC signal cable between
the master and slave BSC systems is
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value
Value
Range
Single
Single,
Parallel
12
1–20
0
0–19
Normal
Normal
mode
mode,
ECO,
Self-load
mode,
Converter
mode
± 5%
± 5% to
± 10%
Non-BSC,
Non-BSC
Standard
BSC
mode,
Opt. BSC
card mode
110