Huawei UPS5000-S-600 User Manual page 199

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Table 8-5 Bypass input electrical specifications
Item
Input system
Rated input voltage
Rated frequency
Input frequency
Input system
Table 8-6 Battery specifications
Item
Battery voltage
Battery management
Cold start
Charger output power
Battery string sharing
Batteries with no neutral
wire
Charging voltage
End of discharge (EOD)
voltage
Table 8-7 Output electrical specifications
Item
Output system
Voltage
Issue 05 (2019-12-20)
Specifications
Three-phase, three-wire, and PE; does not support Δ-type
transformer input; supports only Y-type transformer input
380 V AC/400 V AC/415 V AC/420 V AC/480 V AC (line
voltage)
50 Hz or 60 Hz
± 6 Hz (0.5–6 Hz, ± 2 Hz by default)
The mains input and bypass input can share a power source or
use different power sources.
Specifications
360–600 V DC (30–50 batteries, 40 batteries by default). If
there are 36–39 batteries, the output power is derated to 90%. If
there are 30–35 batteries, the output power is derated to 80%.
Intelligent battery management
If a mains outage occurs, batteries can start the UPS to supply
power to loads.
Under rated conditions, the maximum charge power of a
module is 15 kW.
Battery string sharing is supported in a parallel system. No
battery string is shared by default.
Supported
Equalized charging voltage: 2.3–2.4 V/cell. The default
voltage is 2.35 V/cell.
Float charging voltage: 2.23–2.3 V/cell. The default voltage
is 2.25 V/cell.
1.6–1.9 V/cell
Specifications
Three-phase, three-wire, and PE
380 V AC/400 V AC/415 V AC/420 V AC/480 V AC (line
Copyright © Huawei Technologies Co., Ltd.
8 Technical Specifications
191