Huawei UPS5000-S-600 User Manual page 114

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Figure 4-26 RS485 Settings
Item
Address
Baud rate
Parity mode
Stop bit
On the Comm Settings screen, tap ModbusTCP Settings. The ModbusTCP Settings screen
is displayed.
Issue 05 (2019-12-20)
Description
This serial port address is allocated by the user.
Select a baud rate to match the user's network
management conditions onsite.
Verify the validity of RS485 communication
characters. When a device node adopts RS485
communication, ensure that the parity modes
for the device nodes are set to the same mode.
Stop bit in the Modbus communication frame
format. When the UPS is connected over the
serial port Modbus, set this parameter based on
the frame format that the upstream device
Modbus supports.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value
Value
Range
1
1–254
9600,
9600
19200,
115200
None
None,
Odd, Even
1
1, 2
106