Huawei UPS5000-S-600 User Manual page 126

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Item
Number of
battery
strings
Installation
time
Maintenanc
e period (d)
Chg. cur.
limiting
coef. (C10)
Cell float
voltage
(V/cell)
Cell
equalized
volt. (V/cell)
Dis. cur.
0.1C EOD
(V/cell)
Dis. cur.
0.3C EOD
(V/cell)
Dis. cur.
0.5C EOD
(V/cell)
Dis. cur.
1.0C EOD
(V/cell)
Sched.
shallow dis.
test
Shallow dis.
test dis.
ratio (%)
Issue 05 (2019-12-20)
Description
Specifies the number of battery
strings connected in parallel.
A battery maintenance reminder is
displayed when the maintenance time
(counted from the installation time)
comes.
Specifies the interval for reminding
users of battery maintenance. If this
parameter is set to 0, there is no
reminder.
The charging current limit is a
multiple of the battery capacity.
Specifies the battery float charging
voltage.
Specifies the battery equalized
charging voltage.
Specifies the EOD threshold when
the discharging current is 0.1C, 0.3C,
0.5C, and 1.0C respectively.
When certain conditions are met, the
charger shuts down, and batteries
supply power to loads. The system
records the battery discharge data as
the reference for battery capacity and
lifespan.
Set the proportion of the discharge
capacity to the total discharge
capacity. The value is configurable in
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default
Value Range
Value
12 V
30–50
battery: 40
1
1–4
N/A
N/A
0
0–365
0.10
0.05–0.15
2.25
2.23–2.30
2.35
2.30–2.40
1.80
1.80–1.90
1.80
1.80–1.90
1.75
1.75–1.85
1.60
1.60–1.75
Disable
Disable, Enable
20