Huawei UPS5000-S-600 User Manual page 123

Three-phase, three-wire
Hide thumbs Also See for UPS5000-S-600:
Table of Contents

Advertisement

UPS5000-S-600 kVA
User Manual (Three-phase, Three-wire)
Figure 4-37 Bypass Settings
Item
Maximum
bypass
voltage
Minimum
bypass
voltage
Issue 05 (2019-12-20)
Description
When the difference between the
bypass voltage and the rated voltage
exceeds the upper threshold for the
bypass voltage, the system
determines that the bypass voltage is
not normal and that the bypass is
unavailable.
When the difference between the
bypass voltage and the rated voltage
exceeds the lower threshold for the
bypass voltage, the system
determines that the bypass voltage is
abnormal and that the bypass is
unavailable.
Copyright © Huawei Technologies Co., Ltd.
4 User Interface
Default Value
When the
voltage level is
380 V, the
default value is
+15%.
When the
voltage level is
400 V, the
default value is
+15%.
When the
voltage level is
415 V, the
default value is
+10%.
When the
voltage level is
420 V, the
default value is
+10%.
When the
voltage level is
480 V, the
default value is
+10%.
–20%
Value
Range
+10%,
+15%,
+20%,
+25%
–10%,
–15%,
–20%,
–30%,
–40%
115