CONTROL KEYPAD
Fault type symbol
A
(Alarm)
F
(Fault)
AR
(Fault Autoreset)
FT
(Fault Trip)
Table 8-3. Fault types
8.3.4.2
Fault time data record
When a fault occurs the information described above in 8.3.4 is displayed. By pushing the
button right
here you will enter the
menu, some selected important data valid at the time of the fault are recorded. This feature is
intended to help the user or the service person to determine the cause of fault.
The data available are:
Counted operation days
T.1
(Fault 43: Additional code)
Counted operation hours
T.2
(Fault 43: Counted operation days)
Output frequency
T.3
(Fault 43: Counted operation hours)
T.4
Motor current
T.5
Motor voltage
T.6
Motor power
T.7
Motor torque
T.8
DC voltage
T.9
Unit temperature
T.10
Run status
T.11
Direction
T.12
Warnings
T.13
0-speed*
Table 8-4. Fault time recorded data
* Tells the user if the drive was at zero speed (< 0.01 Hz) when the fault occurred
8.3.4.3
Real time record
If real time is set to run on the frequency converter the data items T1 and T2 will appear as follows:
T.1
Counted operation days
T.2
Counted operation hours
24-hour support: +358 (0)40 837 1150 • Email: vacon@vacon.com
This type of fault is a sign of an unusual operating
condition. It does not cause the drive to stop, nor does it
require any special actions. The 'A fault' remains in the
display for about 30 seconds.
An 'F fault' is a kind of fault that makes the drive stop.
Actions need to be taken in order to restart the drive.
If an 'AR fault' occurs the drive will also stop
immediately. The fault is reset automatically and the
drive tries to restart the motor. Finally, if the restart is
not successful, a fault trip (FT, see below) occurs.
If the drive is unable to restart the motor after an AR
fault an FT fault occurs. The effect of the 'FT fault' is
basically the same as that of the F fault: the drive is
stopped.
Fault time data record menu
d
hh:mm:ss
(d)
Hz
(hh:mm:ss)
A
V
%
%
V
°C
yyyy-mm-dd
hh:mm:ss,sss
Meaning
indicated by T.1 T.13. In this
vacon • 57
Menu
8

Hide quick links:

Advertisement

Table of Contents