Common Error Messages For Manual Address Source Configuration; Common Pass Through Error Codes - Allen-Bradley PanelView 1200 Series User Manual

Operator terminals
Table of Contents

Advertisement

Appendix B
Troubleshooting
Message
Baud Rate falls outside of this PLC baud rate
range
Rack Assignment falls outside of this PLC
address range
Invalid Rack Number
Rack Number must be octal
Error code
145
Remote station host is not there, is
disconnected, or is shutdown"
163
Illegal address address does not exist, or
does not point to something usable by this
command"
164
Illegal size; file is wrong size; address is
past end of file"
171
Command cannot be executed"
B-6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com

Common Error Messages for Manual Address Source Configuration

The following table shows a list of common error messages for Manual
Address Source Configurations
Cause
The selected PLC type does not support the
selected Pass Through baud rate.
The selected PLC type does not support the
selected Pass Through rack number.
The selected PLC type does not support the
selected Pass Through rack number.
The rack number must be entered in octal.

Common Pass Through Error Codes

The following table lists some common error codes that can appear when
you're using Pass-Through.
Probable causes
PLC controller is faulted, or PLC program is
corrupted.
The cable is disconnected from the PLC
controller.
The wrong PLC station address was specified.
Using PCMK card, and the KL*.BIN files were
not copied from the PASSTHRU\PCMK directory
to the PASSTHRU directory.
Trying to download through a PLC 5/40 using
PanelBuilder software Version 4.0, where the
PanelView 1200 terminal is assigned a rack
number greater than 7.
Using a PLC controller that has 2 remote I/O
channels, with the PanelView 1200 terminal on
both channels as partial racks.
PLC programming problems such as indirect
addressing or I/O indirection in the PLC
controller. The PLC controller doesn't catch all
illegal indirection.
PLC controller doesn't support Pass Through.
What to do
Ensure that the Manual Address Source Baud
Rate and the Manual Address Source PLC Type
are compatible. To check compatibility, refer to
the previous table.
Ensure that the Manual Address Source Rack
Number and the Manual Address Source PLC
Type are compatible. To check compatibility,
refer to the previous table.
Ensure that the Manual Address Source Rack
Number and the Manual Address Source PLC
Type are compatible. To check compatibility,
refer to the previous table.
Calculate the rack number in octal, and enter
that number.
What to do
Clear PLC faults or reload the PLC program.
Ensure that the cable is connected to the PLC
controller.
Specify the correct PLC station address.
Copy the KL*.BIN files from the
PASSTHRU\PCMK directory to the PASSTHRU
directory
Use PanelBuilder software Version 5.01, or
higher.
Ensure that all rack numbers are on the same
channel. Ensure that you're using Pass Through
Version 3.01.
Try downloading without ladder logic to see if it
works without it. If it works, rewrite the ladder
logic.
See the previous table listing PLC controllers
that support Pass Through.