Installation Notes; Panelview 1200 Terminal Cutouts - Allen-Bradley PanelView 1200 Series User Manual

Operator terminals
Table of Contents

Advertisement

Color
Touch Screen
PanelView 1200 Terminal
Cutouts
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Figure 1.12
Color Touch Screen Terminal Dimensions
PanelView

Installation Notes

PanelView 1200 terminals are installed in a rectangular cut-out in a panel.
Depending on the model, the terminals mount with mounting studs or
mounting clips.
With the stud-mount models (TA4, TC4, KA1, KC1) nuts are provided
with the terminal. A gasket is fixed on the faceplate. Tighten the terminal
down onto the enclosure to compress this gasket. The gasket has built-in
spacers that will not allow it to be over-compressed. You will notice that
the tightening torque increases significantly when you reach the correct
compression. At this point the tightening torque should not exceed 10
inch-pounds.
With the clip-mount touch screen terminals (TA1, TC1), four mounting
clips are provided. Assemble the mounting clips before installing the
terminal.
Use a screwdriver to install two clips on each side. (See Figure 1.16.)
Tighten the screws until the chassis is held snugly in place against the
panel. A torque of 10 inch-pounds provides a good seal. Do not
over-tighten the screws.