Problem
While trying to download an application file, a
PROBLEM window appears stating: Error code
208 was returned by the Pass Through Utility".
Immediately after completing a PLC 5
Pass Through Download, a Minor Fault Status
bit is set in the PLC 5.
Processor
Series
PLC 5/11
All
PLC 5/15
B
PLC 5/20
All
PLC 5/25
A
PLC 5/30
A
PLC 5/40
A
B
PLC 5/60
A
B
PLC 5/250
All
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Cause
The Pass Through Utility has been unable to
establish DH+ communications with the PLC 5.
The rack assignment configuration of the
application file downloaded to the PanelView
1200 terminal did not exactly match the
application file that was overwritten.

PLC Controllers Required for Pass Through

Important Only specific models and revisions of PLC controllers are
capable of the Pass-Through download/upload. Refer to the following table
for compatible models and revisions.
Revision
All
N or later
All
J or later
B or later
E or later
B or later
E or later
B or later
All
Appendix B
Troubleshooting
What to do
Make sure the Programming Terminal DH+
Address" and the PLC DH+ Address" are
properly assigned.
Make sure that you have selected the proper
DH+ Hardware Driver" for your system, and that
the DH+ Driver Card Location" code is correct.
Use the PLC 5 6200 Series software to clear the
Minor Fault; then reconfigure the PLC 5 to
recognize the new rack assignment.
Valid PLC Racks
Baud Rates
3 octal
57.6 kbps
115.2 kbps
230.4 kbps
1-3 octal
57.6 kbps
1 3 octal
57.6 kbps
115.2 kbps
230.4 kbps
1-7 octal
57.6 kbps
1-7 octal
57.6 kbps
115.2 kbps
230.4 kbps
1-17 octal
57.6 kbps
115.2 kbps
230.4 kbps
1-27 octal
57.6 kbps
115.2 kbps
230.4 kbps
1-37 octal
57.6 kbps
115.2 kbps
230.4 kbps