Fuses; Character Set; User Memory; Alarm Relay - Allen-Bradley PanelView 1200 Series User Manual

Operator terminals
Table of Contents

Advertisement

Appendix A
Specifications

Fuses

Character Set

User Memory

Alarm Relay

A-6
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
one for each AC line
accepts either US or European fuse types
user-accessible at rear of terminal
US fuse: BUSS AGC-3, 3 amps, 250 VAC, 1/4" X 1-1/4"
European fuse: BUSS GDB-3, 3 AMPS, 250 VAC, 5 mm x 20 mm
PanelView 1200 terminals support two character sets:
the IBM character set for the keyboard characters, lines, boxes, etc.
another set containing additional characters that allow the terminal to
display objects such as pixel resolution bar graphs and ISA symbols. To
view the extended character set, refer to the appropriate appendix in
your PanelBuilder Development Software User Manual, or
PanelBuilder 1200 Configuration Software for Windows User Manual.
The terminal supports 64K of standard user memory in battery-backed
RAM.
You can install an additional EPROM for application file back-up. You can
install an additional EEPROM for either application file back-up or for
64K of additional application RAM, (bringing the total available RAM to
128K). When the EEPROM is used as additional application RAM, it
cannot be used as application file back-up.
RAM tests can be initiated in the terminal's Unit Tests screen in
Configuration mode.
Memory Checksum tests can be initiated in the terminal's Unit Tests
screen in Configuration mode, and are automatically executed during
terminal power-up as well.
Form-C Contact
250 VAC Max, 8 Amp Continuous
30 VDC Max, 8 Amp Continuous
Minimum Voltage: 1 VDC
Minimum Current: 1 milliamp DC

Advertisement

Table of Contents
loading

Table of Contents