5. Commissioning
5.7.4. Setting the maximum fuel input for
heating system operation
Note: These values for natural gas.
MCA Pro 35
M
Maximum fuel input
F
Factory setting
Q
Fuel input MBH/kW
R
Fan rotation speed (rpm)
MCA Pro 45
M
Maximum fuel input
F
Factory setting
Q
Fuel input MBH/kW
R
Fan rotation speed (rpm)
MCA Pro 65
M
Maximum fuel input
F
Factory setting
Q
Fuel input MBH/kW
R
Fan rotation speed (rpm)
MCA Pro 90
M
Maximum fuel input
F
Factory setting
Q
Fuel input MBH/kW
R
Fan rotation speed (rpm)
MCA Pro 115
M
Maximum fuel input
F
Factory setting
Q
Fuel input MBH/kW
R
Fan rotation speed (rpm)
See the graphs for the relationship between heat input
and speed for natural gas. The speed can be changed
using parameter p17. To do this, proceed as follows:
MCA-Pro ISM Rv.4.1 2/2017
MBH/kW
136.5 /40
114 /33.3
68.3 /20
Q
MBH/kW
204.8 /60
156 /45.7
Q
68.3 /20
MBH/kW
273 /80
235 /68.8
Q
136.5 /40
68.3 /20
MBH/kW
341.3 /100
326 /95.5
273 /80
204.8 /60
Q
136.5 /40
68.3 /20
MBH/kW
399 /117
341.3 /100
273 /80
Q
204.8 /60
136.5 /40
68.3 /20
MCA Pro 45/65/90/115
M
F
0
1500
2500
3500
4500
4100
R
0
1500
2500
3500
4500
R
0
1500
2500
3500
4500
R
0
1500
2500
3500
4500
R
0
1500
2500
3500
4500
R
5500
6500
7500
M
F
5500
6500
7500
5600
M
F
5500
6500
7500
5600
M
F
5500
6500
7500
6400
M
M
F
F
5500
6500
7500
6600
79