Operating the positioner
Enable configuration:
Configuration is locked again if no settings are entered within 120 s.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Limit the signal pressure:
1. Turn
until Code 16 appears.
2. Press
, the code number 16 blinks.
3. Turn
until the required pressure limit
(1.4/2.4/3.7 bar) appears.
4. Press
to confirm.
7.5 Checking the operating range of the positioner
To check the mechanical attachment and the proper functioning, the valve should be moved
through the operating range of the positioner in the
point.
Select manual mode ( ):
1. Turn
until Code 0 appears.
2. Press
, the code number 0 blinks.
3. Turn
until MAN appears.
4. Press
. The positioner changes to the
manual mode ( ).
98
Enable configuration
Default: No
Pressure limit
Default: No
manual mode with the manual set
Operating mode
Default: MAN
EB 8384-5 EN