Limiting The Signal Pressure; Checking The Operating Range Of The Positioner - Samson 3730-3 Mounting And Operating Instructions

Electropneumatic positioner with hart communication
Table of Contents

Advertisement

Operating the positioner

7.4 Limiting the signal pressure

If the maximum actuator force may cause damage to the valve, the signal pressure must be
limited.
Î Do not activate pressure limitation for double-acting actuators (AIR TO OPEN (AtO) fail-
safe position). Default setting is 'No'.
Enable configuration at the positioner before limiting the signal pressure.
Enable configuration:
If no settings are entered within 120 seconds, the enabled configuration function becomes in-
valid.
1. Turn
until Code 3 appears (reading:
No).
2. Press
, the code number 3 blinks.
3. Turn
until YES appears.
4. Press
to confirm (reading: ).
Limit the signal pressure:
1. Turn
until Code 16 appears.
2. Press
, the code number 16 blinks.
3. Turn
until the required pressure limit
(1.4/2.4/3.7 bar) appears.
4. Press
to confirm.

7.5 Checking the operating range of the positioner

To check the mechanical attachment and the proper functioning, the valve should be moved
through the operating range of the positioner in the
point.
98
Enable configuration
Default: No
Pressure limit
Default: No
manual mode with the manual set
EB 8384-3 EN