Decimal Values Of The Modes In The Foundation™ Fieldbus Blocks (Code 48); Decimal Values Of The States In The Foundation™ Fieldbus Blocks (Code 48) - Samson 3730 Series Mounting And Operating Instructions

Electropneumatic positioner with foundation fieldbus communication
Table of Contents

Advertisement

Error codes – Recommended
action
81
Reference graphs
Status classification
Recommended action Check and, if necessary, perform a new reference test.
11.5 Decimal values of the modes in the FOUNDATION™ fieldbus
blocks (Code 48)
Mode
Decimal value
AUTO
8
AUTO/CAS
12
AUTO/RCAS
134
O/S
128
MAN
16
11.6 Decimal values of the states in the FOUNDATION™ fieldbus
blocks (Code 48)
Status englisch
Good (NC) – Non-specific
Good (NC) – Active block alarm
Good (NC) – Active advisory alarm
Good (NC) – Active critical alarm
Good (NC) – Unack block alarm
Good (NC) – Unack advisory alarm
Good (NC) – Unack critical alarm
Uncertain – Non-specific
EB 8384-5 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
Error occurred during plotting the reference graphs for drive signal y
steady-state or drive signal y hysteresis.
• Reference test canceled
• Reference line for drive signal y steady-state or drive signal y hyster-
esis was not adopted.
[No message]
Decimal value
128
132
136
140
144
148
152
64
Appendix