11.4 Error codes

Initialization errors
Error codes –
Recommended action
50 x > permissible range Value of measuring signal too high or too low; the lever operates near its
Status classification
Recommended action Check attachment and pin position, set operating mode from SAFE to
51 Δx < permissible
range
Status classification
Recommended action Check attachment and re-initialize the positioner.
52 Attachment
Status classification
Recommended action Check attachment and supply pressure. Re-initialize the positioner.
EB 8384-5 EN
Condensed state message active, when prompted, Err appears.
When fault alarms exist, they are displayed here.
mechanical stops.
• Pin not mounted properly
• Bracket slipped in case of NAMUR attachment or positioner is off
center.
Follower plate not mounted properly.
[Maintenance required]
MAN and re-initialize the positioner.
Insufficient measuring span of the lever.
• Pin not mounted properly
• Wrong lever
An angle of rotation smaller than 16° at the positioner shaft only gener-
ates an alarm. An angle below 9° leads to the initialization being can-
celed.
[Maintenance required]
• Invalid positioner attachment
• Rated travel/angle (Code 5) could not be achieved during NOM
initialization (no tolerance downwards permissible).
• Mechanical or pneumatic fault, e.g. wrong lever selected or supply
pressure too low to move to the required position.
[Maintenance required]
Under certain circumstances, it may be possible to check the maximum
travel/angle by entering the actual pin position and then performing a
MAX initialization.
After initialization has been completed, the Code 5 indicates the maxi-
mum achieved travel or angle.