Mounting and start-up
5.11 Mounting the leakage
sensor
Î Refer to Fig. 30
Normally, the control valve is delivered with
positioner and leakage sensor already
mounted.
If the leakage sensor is mounted after the
valve has been installed or it is mounted on-
to another control valve, proceed as de-
scribed in the following.
NOTICE
!
Risk of malfunction due to incorrect fastening.
Fasten the leakage sensor using a torque of
20 ±5 Nm.
Fig. 30: Mounting the leakage sensor
78
3
2
1
The M8 threaded connection on the NAMUR
rib should preferably be used to mount the
sensor (Fig. 30).
Tip
If the positioner was mounted directly onto
the actuator (integral attachment), the
NAMUR interfaces on either side of the valve
yoke can be used to mount the leakage sen-
sor.
The start-up of the leakage sensor is de-
scribed in detail in the Operating Instructions
for EXPERTplus Valve Diagnostics.
1 Leakage sensor
2 Screw
3 Plug connection
EB 8384-5 EN