Setting The Volume Restriction Q; Limiting The Signal Pressure; Checking The Operating Range Of The Positioner - Samson 3730-3 Mounting And Operating Instructions

Electropneumatic positioner
Table of Contents

Advertisement

does not have any effect on the operation of
the positioner.
5.2

Setting the volume restriction Q

4
For actuators smaller than 240 cm
a loading pressure connection at the side
(Type 3271-5), set restriction to MIN
SIDE.
4
For a connection at the back
(Type 3277-5), set restriction to MIN
BACK.
4
For actuators 240 cm
MAX SIDE for a side connection and to
MAX BACK for a connection at the back.
Note! The positioner must re-initialized if the
volume restriction setting is changed after
the positioner has already been initialized.
Adapting the display
The data representation on the positioner
display can be turned by 180°.
If the displayed data appear upside down,
proceed as follows:
Turn the
button until Code 2 appears,
and press the
Code 2 blinks.
2
and larger, set to
Reading direction for right
attachment of pneumatic
connections
Reading direction for left
attachment of pneumatic
connections
button to confirm Code 2 ,
4
Turn
justed to the desired direction, then con-
firm reading direction by pressing the
button.
2
with
5.3

Limiting the signal pressure

If the maximum actuator force may cause
damage to the valve, the signal pressure
must be limited. Select Code 3 to enable
configuration and then access Code 16 to
set the pressure limit to 1.4, 2.4 or 3.7 bar.
5.4
Checking the operating
range of the positioner
To check the mechanical attachment and the
proper functioning, the valve should be
moved through the operating range of the
positioner in the manual operating mode
with the manual reference variable.
1. Turn the
then confirm Code 0 by pressing the
button.
2. Turn the
the display, i.e. manual operating mode,
confirm selected operating mode by
pressing the
Start-up and settings
button until the display is ad-
Code 0
Select
manual operation
Default MAN
Code 1
Position valve using the
rotary pushbutton, the
current angle of rotation is
indicated
button until Code 0 appears,
button until MAN appears in
button.
EB 8384-3 EN