Mounting On Rotary Actuators - Samson 3730 Series Mounting And Operating Instructions

Electropneumatic positioner with foundation fieldbus communication
Table of Contents

Advertisement

5.10.4 Mounting on rotary
actuators
Î Required mounting parts and accesso-
ries: Table 8 on page 27.
Î Refer to Fig. 29
1. Place the lever (1) on the position sensor
in mid-position and hold it in place. Un-
thread the nut (1.1) and remove the lever
together with the disk spring (1.2) from
the sensor shaft.
2. Screw the position sensor (20) onto the
mounting plate (21).
Fig. 29: Mounting on rotary actuators
EB 8384-5 EN
2
1
1.1, 1.2
3. Replace the follower pin (2) normally at-
tached to the lever (1) with the metal fol-
lower pin (Ø 5 mm) from the accessories
and screw it into the hole for pin position
90°.
4. Place the lever (1) and disk spring (1.2)
on the sensor shaft. Place the lever in
mid-position and hold it in place. Screw
on the nut (1.1).
Follow the instructions describing attachment
to the standard positioner in section 5.8.
Instead of the positioner, attach the position
sensor (20) with its mounting plate (21).
20
21
Mounting and start-up
1
Lever
1.1
Nut
1.2
Disk spring
2
Follower pin
20
Position sensor
21
Mounting plate
77