CHAP. 2 - Parameter programming
Pc
Compressor protection contact status
Compressor
switch. When the door is opened the
doC
evaporator fans shut down and the
compressor will continue working for time
doC, after which it will shut down.
Compressor restart time after door
opening. when the door is opened and
after tdo time, it's setted back the normal
tdo
functioning giving door open alarm (Ed).
With tdo=0 the parameter is disabled.
FAN shutdown TEMPERATURE
The fans will stop if the temperature value
Fst
read by the evaporator sensor is higher
than this value.
Fd
Fst differential
Minimum value attributable to setpoint.
LSE
HSE
Maximum value attributable to setpoint.
NO – NC alarm relay switching
tA
AU
Auxiliary/alarm relay control
StA
Temp. setting for aux. relay
Man in cold room alarm
Select input INP1 on the board as
In1
compressor protection alarm or as man in
cold room alarm (contact NC).
Rev. 02-18
safety
time
for
door
USE MANUAL
E. BOARD ECP200 BASE 4/4A
0 = NO
1 = NC
0...5 min
0...240 min
0 = disabled
-45...+45°C
0...+10°C
-45... HSE °C
+45... LSE °C
0 = activates when alarm is
on
1 = deactivates when alarm is
on
0 = alarm relay
1 = manual auxiliary relay
controlled via AUX key
2 = automatic auxiliary relay
managed by StA temp.
setting with 2°C differential
3 = relay disabled / TeleNET
function
4 = pump down function
(see CHAP 5.15)
5 = free voltage contact for
condensing unit (AUX relay
and compressor relay in
parallel)
6 = contact for casing element
control (AUX relay closed
with compressor output
inactive).
7 = relay disabled / Modbus-
RTU function
-45...+45°C
0 = compressor protection
1 = man in room alarm
0 = NO
0
0
+45°C
2°C
-45°C
+45°C
1
0
0
0
Page 9