Advertisement

E. BOARD ECP200 BASE 4/4A
Password type of protection
P1
( active when PA is not equal 0)
Password
PA
(see P1 for the type of protection)
reL
Software release
COMPRESSOR ACTIVATION/DEACTIVATION CONDITIONS
The ECP200 BASE controller activates the compressor when cold room temperature
exceeds setting+differential (r0); it deactivates the compressor when cold room
temperature is lower than the setting. If the Pump-down function is selected (Parameter
AU=4) refer to chapter 2.14 for the compressor activation / deactivation conditions.
To defrost just press the dedicated key (see section 2.2) to activate the elements relay.
Defrosting will not take place if the end-of-defrost temperature setting (d2) is lower than
the temperature detected by the evaporator sensor. Defrosting ends when the end-of-
defrost temperature (d2) or maximum defrost time (d3) is reached.
Page 10

MANUAL DEFROSTING

USE MANUAL
CHAP. 2 - Parameter programming
0 = only display set point
1 = display set point, AUX,
light access
2 = access in programming
not permitted
3 = access in second level
programming not
permitted
0...999
0 = not active
indicates software version
Rev. 02-18
3
0
7
(Read only)