Addressing Dipswitch Configuration For Network Communication; Figure 9 - Input And Output Identification (Modulating Boiler); Figure 10 - Addressing Dipswitch - Prolon M2000 Series Hardware Manual

Boiler controller
Hide thumbs Also See for M2000 Series:
Table of Contents

Advertisement

INT Port: Incoming RS485
Network communication (Modbus)
AO3 - Modulating Boiler Stage 2
(0-10 / 2-10 / 0-5 VDC)
AO2 - Modulating Boiler Stage 1
(0-10 / 2-10 / 0-5 VDC)
AO1 - Pump 2 (ON/OFF) (0-10 VDC)
DO5 - Pump 1
DO4 - Boiler Backup Stage
DO3 - N/A
DO2 - Boiler Stage 2 Enable
DO1 - Boiler Stage 1 Enable

Addressing Dipswitch Configuration for Network Communication

For proper communication, a unique address must be configured on each controller by setting the first 7 switches on the
addressing dipswitch to the desired value.
These switches are numbered from 1 to 7 and represent a binary value from 1 to 64 (1, 2, 4, 8, 16, 32, and 64 respectively).
The last switch (#8) is reserved. The value of each switch that is in the ON position is added together to form the numer-
ical address of the controller.
The example in Figure 9 shows the switches 1, 2 and 4 in the ON position. Therefore, the corresponding values are 1, 2
and 8, giving an address sum of 11.
The Prolon network allows a maximum of 127 addresses; therefore 127 controllers.
REV. 7.2.0 / PL-HRDW-BLR-M2000-C/F-EN

Figure 9 - Input and Output Identification (Modulating Boiler)

Figure 10 - Addressing Dipswitch

Disable Boiler Call (Dry Contact)
Use Max Heat Setpoint (Dry Contact)
Proof of Pump 2 (AO1) (Dry Contact)
Proof of Pump 1 (DO5) (Dry Contact)
Return Water temp sensor (10K thermistor)
Supply Water temp sensor (10K thermistor)
Outside air temperature sensor (10K thermistor)
NET Port: Incoming RS485 Network
communication (Modbus)
Controller's Power Source
(24VAC - Class 2)
10

Advertisement

Table of Contents
loading

Table of Contents