QUICK START
GUIDE
M2000 SERIES
www.proloncontrols.com | info@proloncontrols.com
17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9
REV.2.0
PL-QCK-M2000-EN

Advertisement

loading

Summary of Contents for Prolon M2000 SERIES

  • Page 1 QUICK START GUIDE M2000 SERIES www.proloncontrols.com | info@proloncontrols.com 17 510 rue Charles, Suite 100, Mirabel, QC, J7J 1X9 REV.2.0 PL-QCK-M2000-EN...
  • Page 2 Prolon. All specifications are nominal and may change as design improvements are introduced. Prolon shall not be liable for damages resulting from misapplication or misuse of its products. All trademarks are the property of their...
  • Page 3: Table Of Contents

    Table of Contents Boiler Controller .................4 (PL-M2000-BLR) FlexIO Controller ................6 (PL-M2000-FLX) Heatpump Controller ..........8 (PL-M2000-HP & PL-M2000-HPS) Hydronic Controller ..............10 (PL-M2000-HYD) Make Up Air Controller ............... 12 (PL-M2000-MUA) Rooftop Controller ..........14 (PL-M2000-RTU & PL-M2000-RTUS) Compliance....................... 16 Technical Specifications ..................16 REV.2.0 / PL-QCK-M2000-EN...
  • Page 4: Boiler Controller (Pl-M2000-Blr)

    Boiler Controller (PL-M2000-BLR ) INT Port: Incoming RS485 network communication (Modbus) AO 3 - Valve (0-10 / 2-10 / 0-5 VDC) or backup modulating boiler AO 2 - Modulating boiler (0-10 / 2-10 / 0-5 VDC) AO 1 - Pump 2 (ON/OFF) (0/10VDC) DO 5 - Pump 1 DO 4 - Boiler stage 4 DO 3 - Boiler stage 3...
  • Page 5 Bottom row: common for all inputs Disable Boiler Call (dry contact) Use max heat setpoint (dry contact) Proof of pump 2 (AO1) (dry contact) Proof of pump 1 (DO5) (dry contact) Return water temp sensor (10K thermistor) Supply water temp sensor (10K thermistor) Outside air temperature sensor (10K thermistor) NET Port: Incoming RS485 network...
  • Page 6: Flexio Controller (Pl-M2000-Flx)

    FlexIO Controller (PL-M2000-FLX) INT Port: RS485 network communication (Modbus) Analog output 3 Analog output 2 Analog output 1 Digital output 5 Digital output 4 Digital output 3 Digital output 2 Digital output 1 Bottom row: common for all outputs 32-122 °F (0-50 °C) Non-condensing REV.2.0 / PL-QCK-M2000-EN...
  • Page 7 Bottom row: common for all inputs Analog input 9 Analog input 8 Analog input 7 Analog input 6 Analog input 5 Analog input 4 Analog input 3 Analog input 2 Analog input 1 NET Port: RS485 network communication (Modbus) Controller’s power source (24VAC - Class 2) cULus Listed;...
  • Page 8: Heatpump Controller (Pl-M2000-Hp & Pl-M2000-Hps)

    Heatpump Controller (PL-M2000-HP & PL-M2000-HPS) Incoming INT Port: Prolon communication digital temperature from remote sensor computer - OR - - OR - Incoming RS485 Network Controller network (dual RJ45 and communication terminal blocks) (Modbus) AO3 - Bypass / VSD AO2 - Economizer AO1 - Preheating / Mod.
  • Page 9 Bottom Row: common for all inputs Static pressure (0-5 / 1-5V) (1 / 1.5 / 2 / 2.5 in) Ext dry contact for alarm / CO2 sensor (4-20 mA) External dry contact for proof of fan Zone temperature setpoint (0-10K potentiometer) Zone temperature sensor (10K thermistor) Dry contact for clogged filter / Dry contact for schedule override / Supply water temp (10k therm)
  • Page 10: Hydronic Controller (Pl-M2000-Hyd)

    Hydronic Controller (PL-M2000-HYD) Incoming communication from remote computer -OR- Network Controller (dual RJ45 and terminal Blocks) Analog output 3 (0-10VDC) Analog output 2 (0-10VDC) Analog output 1 (0-10VDC) Digital output 5 (24 VAC) Digital output 4 (24 VAC) Digital output 3 (24 VAC) Digital output 2 (24 VAC) Digital output 1 (24 VAC) Bottom row:...
  • Page 11 Bottom row: common for all inputs Analog input 9 (thermistor / 4-20mA / 0-5VDC) Analog input 8 (thermistor / 4-20mA / 0-5VDC) Analog input 7 (thermistor / 4-20mA / 0-5VDC) Analog input 6 (thermistor / 4-20mA / 0-5VDC) Analog input 5 (thermistor / 4-20mA / 0-5VDC) Analog input 4 (thermistor / 4-20mA / 0-5VDC) Analog input 3 (thermistor / 4-20mA / 0-5VDC) Analog input 2 (thermistor / 4-20mA / 0-5VDC)
  • Page 12: Make Up Air Controller (Pl-M2000-Mua)

    Make Up Air Controller (PL-M2000-MUA) INT Port: Incoming RS485 network communication (Modbus) AO3 - Variable frequency drive AO2 - Cooling AO1 - Modulating heat DO5 - Alarm DO4 - Preheat permission DO3 - Fan DO2 - Outside air damper DO1 - Occupancy (exhaust) Bottom row: common for all outputs 32-122 °F (0-50 °C) Non-condensing...
  • Page 13 Bottom row: common for all inputs CO2 (4-20mA) / Building pressure (0-5VDC) Zone temperature (10K thermistor) Outside temperature (10K thermistor) Supply temperature (10K thermistor) Manual reset Proof of san Proof outside air damper open Proof exhaust 2 / Manual override Proof exhaust 1 NET Port: Incoming RS485 network communication (Modbus)
  • Page 14: Rooftop Controller (Pl-M2000-Rtu & Pl-M2000-Rtus)

    Rooftop Controller (PL-M2000-RTU & PL-M2000-RTUS) RTUS Incoming INT Port: Prolon communication digital temperature from remote sensor computer - OR - - OR - Incoming RS485 Network Controller network (dual RJ45 and communication terminal blocks) (Modbus) AO3 - Bypass / VSD AO2 - Economizer AO1 - Preheating / Mod.
  • Page 15 Bottom row: common for all inputs Static pressure (0-5 / 1-5V) (1 / 1.5 / 2 / 2.5 in) CO2 sensor (4-20 mA) External dry contact for proof of fan Zone temperature setpoint (0-10K potentiometer) Zone temperature sensor (10K thermistor) Mixed air temp (10K therm) / Dry contact for clogged filter / Dry contact for schedule override / Auxiliary temp input (10K thermistor)
  • Page 16: Compliance

    Compliance • cULus Listed; UL 916 Energy Management Equipment, File E364757, Vol.1 • CAN/CSA-C22.2 No. 2015-12, Signal Equipment • FCC Compliant to CFR47, Part 15, Subpart B, Class B • Industry Canada (IC) Compliant to ICES-003, Issue 5: CAN ICES-3 (B) / NMB-3(B) •...