Power Source & Network
Power Source
The M2000 controller is powered by a 24 VAC power supply (class 2) by connecting the common (''C'' wire) to the "COM"
terminal and the live (''R'' wire) to the "24 VAC" terminal (see Figure 14). The common for all inputs and outputs is the
same as the power source's common. All output power sources also originate from the source transformer (class 2).
Network Communication
The Prolon M2000 Boiler controller is designed to work standalone or networked with Prolon master controllers. When
networked, the master transmits the occupancy status, outside temperature and math demand in real-time. The
network connections are made using the network terminal block located on the M2000 controller (see Figure 15).
REV. 7.2.0 / PL-HRDW-BLR-M2000-C/F-EN
24VAC
Figure 17 - Connecting the 24VAC Power Source
Figure 18 - Connecting to the Network
( R )
To transformer (class 2)
( C )
( A )
Towards
RS485
Network
( B )
15