8.3.2

PROFIBUS device configuration

Device configuration
In the case of PROFIBUS, the structure of the hardware in the device configuration is as
follows:
Slot
Number
The device configuration rules are as follows:
● CIM
The CIM module includes the PROFIBUS-connection and is permanently present in
slot 1.
● PM
The CIM I/O module is present in slot 2. If no I/O module PM is used, an empty space
must be configured here.
● POM
A maximum of 24 POMs can be operated on one CIM.
Note
The device configuration in the project engineering must match the actual configuration of
the HCS. Otherwise the system cannot start up.
Restrictions for PROFIBUS connection
The following functions are not available or only available with limited functionality with a
PROFIBUS connection:
● Configuration control is not available
● Phase control cannot be configured for operation of a POM4320
● Operation of a POM4320 Highend is not possible
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
8.3 Device/hardware configuration in the TIA Portal
CIM
PM
POM 1
1
2
3
Configuring/Programming
POM 2
POM 3
...
4
5
...
Last
POM
n
85