Servicing and maintenance
12.2 Firmware update
Observe the following information when updating the firmware:
Requirements
The following conditions must be met for you to carry out an update:
Connect the PC to an Ethernet port (X1 or X2) of the CIM.
Either the Central Interface Module (CIM) must be assigned an IP address
(delivery state 0.0.0.0), or the CIM must have been in operation on a PROFINET CPU
(IP address from PROFINET configuration).
Before the update, the connection to the CPU must be stopped or interrupted.
Note
If the connection is not interrupted, an error message appears in the PC tool, but this can be
delayed.
CIM
The update encompasses two firmware parts and is not completed until both parts have
been successfully loaded.
After the update, the HCS4300 restarts automatically. Only in the event of a fault when the
update has not been correctly completed do you have to restart the HCS4300.
POM
In a firmware update, new firmware is downloaded to all power output modules (POMs)
operated on a Central Interface Module (CIM).
After the update, the HCS4300 restarts automatically. Only in the event of a fault when the
update has not been correctly completed do you have to restart the HCS4300.
I/O module PM:
In the event of a firmware update, new firmware is loaded into the inserted PM. After the
update, the HCS4300 restarts automatically. Only in the event of a fault, if the update has
not been correctly completed, is it necessary to restart the HCS4300.
Firmware update via TIA Portal
An update is possible as of TIA Portal V16. You can download the updates files from the
Siemens Service&Support area (https://support.industry.siemens.com/cs/start?lc=en-WW).
See also
SHB_ET200SP (https://support.industry.siemens.com/cs/ww/en/view/58649293)