Communications
10.3 Transfer of diagnostic alarms to the controller
PM error codes
Error code
(hex)
0001
0006
0007
0008
0011
5101
510C
5112
Note
The following applies for PM4000 DI/DO:
The error codes for short-circuit and wire break are each signaled for one group of 4
channels only. The number of the first channel of the group of 4 is entered as the channel
number.
Causes of error and solutions
You will find information about possible causes of error and solutions in section Fault
reporting through diagnostics data (Page 146).
Note
The following applies to channel faults 0x5104 to 0x5107 and 0x510C:
If a fault status changes on a channel, the first fault to be reported is retained.
144
Description
Short-circuit
Wire break
Measurement range, high limit exceeded
Measurement range, low limit violated
No supply voltage
Communication error on HCS bus
Undefined error
Polarity reversal at measuring input
PM
Temperature
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
PM DI/DO
PM U/I