Siemens SIPLUS HCS Series Operating Instructions Manual page 105

Io systems for heating elements, heating control system
Hide thumbs Also See for SIPLUS HCS Series:
Table of Contents

Advertisement

The associated control data record DS196 must be pre-assigned as follows:
Byte
0
1
2
3
4
5
6
7
8
...
28
The data record can also be written in abbreviated form with length 4+4; the last entry is
byte 7 in this case.
In an error-free case, the feedback data record DS197 contains the following entries:
Byte
0
1
2
3
4
5
6
7
8
...
28
SIPLUS HCS4300 PROFINET/PROFIBUS DP
Operating Instructions, 10/2019, A5E35452705A/005
Element
Block length
Block ID
Version
Version
Slot 1 of station master
Slot 2 of station master
Slot 3 of station master
Slot 4 of station master
Slot 5 of station master
...
Slot 25 of station master
Element
Block length
Block ID
Version
Version
Slot 1 of station master
Slot 2 of station master
Slot 3 of station master
Slot 4 of station master
Slot 5 of station master
...
Slot 25 of station master
Code
Description
4 + 25
Header
196
1
0
1
PM available
2
POM available
0
POM is not inserted in the station options
0
POM is not inserted in the station options
0
Module not available
0
Module not available
Code
Description
4 + 50
Header
197
2
0
1
Module is actually not available
1
Module is actually available
1
Module is actually not available
1
Module is actually not available
1
Module is actually available
1
Module is actually not available
Configuring/Programming
8.5 Configuration control
103

Advertisement

Table of Contents
loading

This manual is also suitable for:

Siplus hcs4300 profinetSiplus hcs4300 profibus

Table of Contents