Operational Requirements; Site Requirements; Space And Airflow Requirements - HPE AR44z User Manual

Table of Contents

Advertisement

10. As a best practice, Hewlett Packard Enterprise recommends that you install the latest
firmware, drivers, and system software before using the server for the first time.
To get the latest firmware and software updates, see the server support page:
https://www.hpe.com/support/ar44z
11. Register the system (https://myenterpriselicense.hpe.com).

Operational requirements

Site requirements

The server must be located in a computer room or server room. The room must:
Be only accessible to authorized technicians trained the room restriction reasons and precautions.
Be within an area that is ideally locked or at minimum not accessible to unauthorized personnel.

Space and airflow requirements

To allow for servicing and adequate airflow, observe the following space and airflow requirements when
deciding where to install a rack:
Leave a minimum clearance of 63.5 cm (25 in) in front of the rack.
Leave a minimum clearance of 76.2 cm (30 in) behind the rack.
Leave a minimum clearance of 121.9 cm (48 in) from the back of the rack to the back of another rack
or row of racks.
Hewlett Packard Enterprise servers draw in cool air through the front door and expel warm air through the
rear door. Therefore, the front and rear rack doors must be adequately ventilated to allow ambient room
air to enter the cabinet, and the rear door must be adequately ventilated to allow the warm air to escape
from the cabinet.
CAUTION: To prevent improper cooling and damage to the equipment, do not block the ventilation
openings.
When vertical space in the rack is not filled by a server or rack component, the gaps between the
components cause changes in airflow through the rack and across the servers. Cover all gaps with
blanking panels to maintain proper airflow.
CAUTION: Always use blanking panels to fill empty vertical spaces in the rack. This arrangement
ensures proper airflow. Using a rack without blanking panels results in improper cooling that can
lead to thermal damage.
CAUTION: If a third-party rack is used, observe the following additional requirements to ensure
adequate airflow and to prevent damage to the equipment:
Front and rear doors—If the 42U rack includes closing front and rear doors, you must allow
5,350 sq cm (830 sq in) of holes evenly distributed from top to bottom to permit adequate airflow
(equivalent to the required 64 percent open area for ventilation).
Side—The clearance between the installed rack component and the side panels of the rack must
be a minimum of 7 cm (2.75 in).
20
Setup

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ar64z

Table of Contents