Appendix E: Nfpa Standard-Specific Requirements - Fire-Lite MS-9200(C) Instruction Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200(C):
Table of Contents

Advertisement

NFPA Standard-Specific Requirements
Appendix E
The Fire•Lite MS-9200 has been designed for use in commercial, industrial and institutional applications and meets
the requirements for service under the National Fire Protection Association (NFPA) Standards outlined in this Appen-
dix. The minimum system components required for compliance with the appropriate NFPA standard are listed
below:
MS-9200 Control Panel
Contains the main control board, cabinet (backbox and door), main power supply transformer and power supply.
Batteries
Refer to "Power Supply Calculations" on page 61, for Standby Power Requirements.
Initiating Devices
Connected to one of the control panel's Initiating Device Circuits.
Notification Appliances
Connected to the control panel's Notification Appliance Circuit via a control module.
The following additional equipment if needed for compliance with the NFPA 72 standards listed below:
NFPA 72 National Fire Alarm Standards for:
Fire Alarm Systems for Central Station Service (Protected Premises Unit) and Remote Station Service requires:
MS-5012 for connection to a compatible listed Central Station DACR or Protected Premises Receiv-
ing Unit. This unit must be installed as outlined in Figure E-1, "Central Station Service Using MS-
5012," on page 78.
OR
UDACT-F may be installed as illustrated in Refer to Figure 2-11, "UDACT-F Mounting to MS-
9200," on page 30 and Figure 2-12, "External UDACT-F Mounting in ABS-8RF," on page 31.
OR
411UD may be installed as illustrated Figure E-2, "Fire•Lite MS-9200 Connection to 411-UD," on
page 79.
NFPA 72 Auxiliary Fire Alarm System
RTM-8F Relay/Transmitter Module for connection to a compatible listed Local Energy Municipal Box. This unit
must be installed as outlined in Figure E-3, "Municipal Box Connected to RTM-8F Relay Transmitter Module," on
page 80.
NFPA 72 Remote Station Fire Alarm System
RTM-8F Relay/Transmitter Module for connection to the Fire•Lite RS82 Remote Station Receiver. See Figure E-4,
"Remote Station Connection Using RTM-8F Module," on page 81, for installation instructions for this unit.
NFPA 72 Proprietary Fire Alarm System
MS-9200 Alarm, Trouble and Supervisory contacts connected to Transmitter(s). See Figure E-5, "Proprietary Protec-
tive Signaling System," on page 82, for installation instructions for this unit.
NFPA Standard-Specific Requirements
Document #51003
Rev.E
01/11/02
P/N 51003:E
77