Components
Standard
Optional XRM-24
Batteries
The MS-9200 cabinet provides space for two batteries
up to 12 Amp Hour. 18 AH batteries require use of the
Fire•Lite BB-17F or similar UL listed battery cabinet.
The newer versions of the MS-9200 main circuit board,
which incorporate jumper JP1 for disabling the FACP
charger, can use the CHG Series chargers for charging
25 to 120 AH batteries. Batteries must be ordered sep-
arately and require use of the Fire•Lite BB-55F UL
listed battery cabinet.
1.5.1 Intelligent Addressable Detectors: Newer Series
Intelligent, addressable detectors provide information to the control panel on an SLC Signaling Line Circuit (refer to
the SLC Wiring Manual for detailed information on device installation, wiring and operation). This allows the con-
trol panel to continually process the information to determine the status (alarm, trouble or normal) of each detector.
Each detector responds to an SLC address that is set in the detector head using built-in rotary decimal switches which
can be set to a maximum address of 99. Note that a blinking LED on an intelligent detector indicates communication
between the detector and the control panel. Refer to the Fire•Lite Device Compatibility Document for a list of
approved detectors.
Smoke Detectors (Photoelectric)
The SD350 is an intelligent, addressable low profile photoelectric smoke detector which provides smoke sensing uti-
lizing optical sense technology. The detector sends a unique 'type' code to aid the automatic programming feature in
the control panel. The SD350T includes a 135
Smoke Detector (Ionization)
The CP350 is an intelligent, addressable low profile ionization smoke detector which measures the level of combus-
tion products in its chamber using the 'ionization principle.' The detector sends a unique 'type' code to aid the auto-
matic programming feature in the control panel.
Smoke Detector (Duct)
The D350P is an intelligent, addressable photoelectric duct smoke detector. The D350RP includes an alarm relay.
Detector Bases
The B501BH is a standard sounder base and the B501BHT is a temporal tone sounder base for intelligent,
addressable smoke detectors.
The B224RB is a relay base with one Form-C relay for intelligent, addressable smoke detectors. It may be used to
control auxiliary functions such as damper control and elevator recall.
The B224BI is an isolator base for intelligent, addressable smoke detectors. It functions similar to the I300 isolator
module which allows loops to operate under fault conditions and automatically restore when the fault is removed.
Detector Annunciator
The RA400Z is a remote single LED annunciator that can be wired directly to an addressable detector for annuncia-
tion of that detector's alarm status.
14
Transformer Assembly
One 100VA transformer is provided standard with the panel
(3.6 amps maximum). An optional 100 VA transformer
XRM-24 (XRM-24E for the MS-9200E) is available to
provide maximum accessory power (6.6 amp total).
Battery Cable P/N 75287
O
F fixed thermal sensor.
Document #51003