Accessories

PK-9200W Kit for Local Downloading
The PK-9200W Programming Utility can be used to program an MS-9200 directly from most IBM PC/XT/AT or
compatible computers, including laptops and portables, equipped with a serial port. MS-9200 program files can also
be created and stored on the PC, then downloaded to the control panel. The PK-9200W Kit includes the MS-9200
Windows based Programming Utility software on four 3½" disks and the Instruction Manual P/N 50684. Older ver-
sion of the MS-9200 main circuit board, which do not have connector TB7, require separate purchase of the PIM-24
Interface module.
UDACT-F Universal Digital Alarm Communicator/Transmitter
The UDACT-F transmits system status to UL listed Central Station receivers via the public switched telephone net-
work. The UDACT-F is compact in size and may be mounted inside the host control panel or may mount externally
in a separate cabinet. ACS (EIA-485) annunciator communications bus and filtered 24 volt connections are required.
The UDACT-F transmits 198 points or 56 zones when connected to the MS-9200. The MS-9200 requires firmware
P/N 73580 or greater in order to be compatible with the UDACT-F. Refer to Figure 2-11, "UDACT-F Mounting to
MS-9200," on page 30, and Figure 2-12, "External UDACT-F Mounting in ABS-8RF," on page 31, for wiring details
and "System Edit" on page 45, for information on programming the MS-9200 for use with the UDACT-F.
Annunciator/Display Interface
The LCD-40 Series Remote Fire Annunciator and other Terminal Mode annunciators connect to TB7 on the
MS-9200 main circuit board. Refer to "LCD-40 Series Annunciator Wiring" on page 72, for wiring details and "Sys-
tem Edit" on page 45, for information on programming the MS-9200 for use with the LCD-40.
Older versions of the MS-9200 main circuit board will not have connector TB7. These boards require connection of
DIM-485 in order to connect an LCD-40 Series annunciator. The DIM-485 plugs into connector J11 located on the
top right side of the MS-9200 main circuit board. Note that the DIM-485/LCD-40 cannot be used simultaneously
with the PIM-24 module.
1.7
Accessories
1.7.1 Dress Panel
A dark blue dress panel, DP-1-R, is available as an option (required for Canadian installations and included with the
MS-9200C). The dress panel restricts access to the system wiring while allowing access to the membrane switch
panel.
Note that the MS-9200 Addressable Fire Control Panel installed with the dress panel, has received Factory Mutual
(FM) approval. It is important to note that FM approval is contingent on the proper installation of the dress panel.
17
Document #51003
Rev.E
01/11/02
P/N 51003:E

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200e

Table of Contents