ACS and LDM Series Wiring
Appendix D
The following illustrations show the various configurations which may be wired utilizing ACS Series Annunciators.
LDM Series Annunciators may be used in a similar manner. All illustrations show power supplied to annunciators by
the MS-9200. For system applications requiring greater than the 300 mA of nonresettable power the MS-9200 can
supply, use the Fire•Lite FCPS-24F/E Field Charger Power Supply.
The following figure shows a configuration which provides 56 zones of alarm and trouble indications, remote
Acknowledge/Step, Alarm Silence, Drill and System Reset keys, System Supervisory, AC Fail, and Trouble indica-
tions. Use AKS-1F keyswitch to prevent unauthorized actuation of control switches. Refer to the AFM Manual for
further details.
ACM-16ATF
8 Zones (Alarm & Trouble)
4 switches IACK, SIL,
DRILL, RESET), System
Trouble LED, On-Line/Off-
Line Power LED, Piezo
sounder
Annunciator Power - 12 to 18 AWG
2-wire EIA-485 circuit -
max. 6,000 ft. @ 16 AWG
24V UNREG 24V NONRS 24V RST
BELL 2 POWER
BELL 1 POWER
SUPV
ALARM
TROUBLE
+ - + - + -
B+ A+ A- B-
B+ A+ A- B-
NO C NO NC C NO NC C
T
T
T
B
B
B
4
2
1
J17
J19
JP1
JP4
JP3
J3
TB8
SW1
- +
CAUTION
GNDFAULT
HIGH VOLTAGE
BATTERY
ACS and LDM Series Wiring
AEM-16ATF
Ribbon
Cable
16 Zone (Alarm & Trouble)
PC/PRINTER TERM COMM
ACS
SHIELD
SLC
SLC
OUT+ IN+ OUT- IN-
1 COMM 2
A
B B+ A+ B- A-
T
T
T
T
B
B
B
B
3
7
5
6
Data Communication Port:
EIA-485 @ 20K Baud
J16
MS-9200
SW2
J6
SW3
Document #51003
AEM-16ATF
Ribbon
Cable
16 Zone (Alarm & Trouble)
Ribbon
Ribbon
Cable
Cable
Rev.E
01/11/02
P/N 51003:E
AEM-16ATF
Ribbon
Cable
16 Zone (Alarm & Trouble)
Ribbon
Cable