14
Device Description
power contacts used as blade contacts. It then provides this potential to
subsequent I/O modules via the power contacts used as spring contacts.
Pos : 18.12 /Serie 750 ( WAGO-I/O- SYST EM)/Wi chtig e Erl äuter ung en/Sic her hei ts- und s onstige Hi nweise/Ac htung/Ac htung: Maxi maler Str om Leistungs kontakte 10 A @ 3\mod_1226499143500_21.doc @ 25029 @ @ 1
Do not exceed maximum current via power contacts!
The maximum current to flow through the power contacts is 10 A.
Greater currents can damage the power contacts.
When configuring the system, ensure that this current is not exceeded. If
exceeded, an additional potential feed module must be used.
Pos : 18.13 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Versorgung/Anordnung unter Ber üc ksic htigung der Leis tungs kontakte beliebig @ 3\mod_1233756233468_21.doc @ 27099 @ @ 1
With consideration of the power jumper contacts, the individual modules can be
arranged in any combination when configuring the fieldbus node. An arrangement
in groups within the group of potentials is not necessary.
Pos : 18.14 /Serie 750 ( WAGO-I/O- SYST EM)/Gerätebeschr eibung/Einl eitung/Einsatzbereic h/Eins atzbereic h 750- xxxx alle Koppler/C ontroll er ohne Ei nschr änkung @ 3\mod_1232541691906_21.doc @ 26522 @ @ 1
The I/O module 750-512 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Pos : 19 /D okumentation allgemei n/Glieder ungs elemente/---Seitenwec hs el--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-512 2DO 230V AC 2.0A/ Relay 2NO