40
Use in Hazardous Environments
Pos : 72.18 /Serie 750 ( WAGO-I/O- SYST EM)/Ei nsatz i n Ex-Bereic hen/Besonder e Beding ungen für den sicher en Ex- Betri eb gem. AT EX-Z ertifi kat TÜ V 12 ATEX 106032x @ 14\mod_1360742619838_21.doc @ 111760 @ 3 @ 1
7.2.2
Special conditions for safe use (ATEX Certificate TÜV 12
ATEX 106032 X)
1.
For use as Gc- or Dc-apparatus (in zone 2 or 22) the Field bus Independent
I/O Modules WAGO-I/O-SYSTEM 750-*** Ex i shall be erected in an
enclosure that fulfils the requirements of the applicable standards (see the
marking) EN 60079-0, EN 60079-11, EN 60079-15 and EN 60079-31.
For use as group I electrical apparatus M2 the apparatus shall be erected in
an enclosure that ensures a sufficient protection according to EN 60079-0
and EN 60079-1 and the degree of protection IP64.
The compliance of these requirements and the correct installation into an
enclosure or a control cabinet of the devices shall be certified by an ExNB.
2.
Measures have to be taken outside of the device that the rating voltage is not
being exceeded of more than 40 % because of transient disturbances.
3.
The connecting and disconnecting of the non-intrinsically safe circuits is
only permitted during installation, for maintenance or for repair purposes.
The temporal coincidence of explosion hazardous atmosphere and
installation, maintenance resp. repair purposes shall be excluded.
4.
For the type 750-633/000-003 the following shall be considered: The
Interface circuits shall be limited to overvoltage category I/II/III (non
mains/mains circuits) as defined in EN 60664-1.
Pos : 72.19 /D okumentati on allgemein/Gli ederungsel emente/---Seitenwec hsel--- @ 3\mod_1221108045078_0.doc @ 21810 @ @ 1
WAGO-I/O-SYSTEM 750
750-512 2DO 230V AC 2.0A/ Relay 2NO