Auto-Reclose Example 2 (Use Of Quicklogic With Ar) - Siemens Solkor 7PG2113 Technical Manual

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

5.1.2

Auto-Reclose Example 2 (Use of Quicklogic with AR)

Requirement: The relay at location 'A' is required to provide a reclose sequence of 2 Instantaneous followed by 2
delayed recloses. Where the fault current level is between the values 'I1' and 'I2' and the first trip is initiated from
the 51-1 (IDMT) element, the IDMT characteristic should trip the CB and lockout the auto-reclose.
Typical settings are:
CONTROL & LOGIC > AUTORECLOSE PROT'N:
79 P/F Inst Trips: 50-1
79 P/F Delayed Trips: 51-1
CONTROL & LOGIC > AUTORECLOSE CONFIG > P/F SHOTS
79 P/F Prot'n Trip 1 : Inst
79 P/F Prot'n Trip 2 : Inst
79 P/F Prot'n Trip 3 : Delayed
79 P/F Prot'n Trip 4 : Delayed
The above settings are suitable at values of fault current above 'I2' however were a fault to occur with a current
value between 'I1' and 'I2' this would be detected by the 51-1 element only. As Prot'n Trip 1 = Inst then the relay
would trip and reclose whereas it is required to lockout for this occurrence.
To provide a lockout for the above faults an additional element 50-2 with identical settings to 50-1 is assigned as
a Delayed Trip and is used in conjunction with the Quick Logic feature i.e.
OUTPUT CONFIG>OUTPUT MATRIX: 51-1 = V1
OUTPUT CONFIG>OUTPUT MATRIX: 50-2 = V2
OUTPUT CONFIG>OUTPUT MATRIX: E1 = V3
CONTROL & LOGIC>QUICK LOGIC: E1 = V1.!V2
INPUT CONFIG>INPUT MATRIX: 79 Lockout = V3
©2010 Siemens Protection Devices Limited
Figure 5.1-2 Example of Logic Application
7PG2113/4/5/6 Solkor Applications Guide
Chapter 7 Page 40 of 49