4.7
Current Protection: Under-Current (37)
Two under-current elements are provided 37-1 & 37-2.
Each phase has an independent level detector and current-timing element. 37-n Setting sets the pick-up current.
An output is given after elapse of the 37-n Delay setting.
Operation of the under-current elements can be inhibited from:
Inhibit 37-n
Figure 4.7-1 Logic Diagram: Relays with 4 Current Inputs Undercurrent Detector (37)
Figure 4.7-2 Logic Diagram: Relays with 1 Current Inputs Undercurrent Detector (37)
©2010 Siemens Protection Devices Limited
A binary or virtual input.
&
c
<
<
<
7PG2113/4/5/6 Solkor Description of Operation
1
Chapter 1 Page 52 of 80