Siemens Solkor 7PG2113 Technical Manual page 134

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

2.11.3 Operate and Reset Time
Attribute
Starter operate time (≥ 2xIs)
t
Operate time
op
Reset time
Repeatability
Overshoot time
Disengaging time
Figure 2.10-1 shows the operate times for the four IEC IDMTL curves with a time multiplier of 1.
Figures 2.10-2 and 2.10-3 show the ANSI operate and reset curves. These operate times apply to non-directional
characteristics. Where directional control is applied then the directional element operate time should be added to
give total maximum operating time.
©2010 Siemens Protection Devices Limited
char = IEC-NI,
IEC-VI,
IEC-EI,
IEC-LTI
char = ANSI-MI,
ANSI-VI,
ANSI-EI
char = DTL
ANSI DECAYING
t
res
7PG2113/4/5/6 Performance Specification
Value
30 ms, ± 20ms
K
=
×
, ± 5 % absolute or ± 30 ms,
t
Tm
[ ]
α
op
I
1
Is
IEC-NI : K = 0.14, α = 0.02
for char =
IEC-VI : K = 13.5, α = 1.0
IEC-EI : K = 80.0, α = 2.0
IEC-LTI : K = 120.0, α = 1.0
A
=
+
×
t
[ ]
B
Tm
op
P
I
1
Is
for char = ANSI-MI : A = 0.0515, B = 0.114, P = 0.02
ANSI-VI : A = 19.61, B = 0.491, P = 2.0
ANSI-EI : A = 28.2,
, ± 1 % or ± 20ms
t
d
R
=
×
, ± 5 % absolute or ± 30 ms,
t
Tm
[ ]
res
2
I
1
Is
for char = ANSI-MI : R = 4.85
ANSI-VI : R = 21.6
ANSI-EI : R = 29.1
, ± 1 % or ± 20ms
t
res
± 1 % or ± 20ms
< 40 ms
< 50 ms
, ± 5 % absolute or ± 30 ms,
B = 0.1217, P = 2.0
Chapter 3 Page 31 of 42