Siemens Solkor 7PG2113 Technical Manual page 241

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

Calculated Timing values in seconds for TM =1.0
Curve
IEC-NI
IEC-VI
IEC-EI
IEC-LTI
ANSI-MI
ANSI-VI
ANSI-EI
Note that the operate time may be subject to the Minimum op time setting for the element and/or may have a
Follower DTL applied.
If VTS action is set to BLOCK, this option should be tested. Apply balanced voltage and current. Reduce a-phase
voltage to cause a VTS condition. Increase a-phase current and check that the element does not operate.
If VTS action is set to Non-Directional, this option should be tested. Apply balanced voltage and current. Reduce
a-phase voltage to cause a VTS condition. Increase a-phase current and check that the element operates at its
normal setting. Reverse the voltage phase direction whilst checking that the element does not reset.
2.9.3.1
Element Blocking
The Sensitive Earth Fault elements can be blocked by Binary Input Inhibit and VT Supervision. The Characteristic
can be made non-directional by VT Supervision. This functionality should be checked.
Element
51SEF-1
51SEF-2
51SEF-3
51SEF-4
50SEF-1
50SEF-2
50SEF-3
50SEF-4
©2012 Siemens Protection Devices Limited
2 xIs
10.03
13.50
26.67
120.00
3.80
7.03
9.52
Table 2.9-4
Standard Timings
BI Inhibits
Table 2.9-5
51SEF Element Blocking
7PG2113/4/5/6 Commissioning & Maintenance
5 xIs
4.28
3.38
3.33
30.00
1.69
1.31
1.30
VTS action
Chapter 6 Page 43 of 77