Binary Outputs; Leds - Siemens Solkor 7PG2113 Technical Manual

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

2.3

Binary Outputs

Binary Outputs are mapped to output functions by means of settings. These could be used to bring out such
digital signals as trips, a general pick-up, plant control signals etc.
All Binary Outputs are Trip rated
Each can be defined as Self or Hand Reset. Self-reset contacts are applicable to most protection applications.
Hand-reset contacts are used where the output must remain active until the user expressly clears it e.g. in a
control scheme where the output must remain active until some external feature has correctly processed it.
Notes on Self Reset Outputs
With a failed breaker condition the relay may remain operated until current flow in the primary system is
interrupted by an upstream device. The relay will then reset and attempt to interrupt trip coil current flowing
through an output contact. Where this level is above the break rating of the output contact an auxiliary relay with
heavy-duty contacts should be utilised.
2.4
LED
S
In the Output Configuration menu LEDs can be mapped to output functions by means of settings. These could be
used to display such digital signals as trips, a general pick-up, plant control signals etc.
Each LED can be defined as Self or Hand Reset. Hand reset LEDs are used where the user is required to
expressly acknowledge the change in status e.g. critical operations such as trips or system failures. Self-reset
LEDs are used to display features which routinely change state, such as Circuit-Breaker open or close.
The status of hand reset LEDs is retained in capacitor-backed memory in the event of supply loss.
©2010 Siemens Protection Devices Limited
7PG2113/4/5/6 Solkor Applications Guide
Chapter 7 Page 18 of 49