Emissions; Immunity - Siemens Solkor 7PG2113 Technical Manual

Feeder protection
Hide thumbs Also See for Solkor 7PG2113:
Table of Contents

Advertisement

1.5.2

Emissions

IEC 60255-25
1.5.2.1
Radiated Emissions: Enclosure
Type
30 to 230 MHz
230 to 1000 MHz
1.5.2.2
Radiated Emissions: Conducted
Type
0.15 to 0.5 MHz
0.5 to 30 MHz
1.5.3

Immunity

1.5.3.1
Auxiliary DC Supply Variation
IEC 60255-11
Type of Phenomena
Voltage Dips
Voltage Interruptions
Alternating
Component In DC
(Ripple)
Gradual Shut-down/
Start-up
Reversal of DC
Power Supply polarity
Key:
RV = Residual Voltage Test Value. Two conditions: (a) range voltage low-20% and
1
No effect on relay performance
2
Restart with no mal-operation, loss of data or relay damage
1.5.3.2
High Frequency Disturbance
IEC 60255-22-1
Type
Common (longitudinal) mode
Series (transverse) mode
1.5.3.3
Electrostatic Discharge
IEC 60255-22-2 Class 4
©2010 Siemens Protection Devices Limited
Limits at 10 m, Quasi-peak
40 dB(μV/m)
47 dB(μV/m)
Quasi-peak
79 dB(μV)
73 dB(μV)
Test Specifications
0% RV
40% RV
70% RV
0% RV
15% max and min RV
Max & min RV to 0V
0V
0V to min & max RV
Max reversed RV
(b) range voltage high +20%
7PG2113/4/5/6 Performance Specification
Duration
50ms
Normal Operation
(Claimed)
Normal operation
200ms
below the relay minimum voltage then Relay
2
Restart
Normal operation
500ms
below the relay minimum voltage then Relay
2
Restart
5s
Relay Reset
Continuous
Normal operation
60s
Relay Reset
5minutes
Relay Off
60s
Relay Restart
1minute
After correcting polarity, Relay Restart
Level
2.5 kV
1.0 kV
Limits
Average
66 dB(μV)
60 dB(μV)
Declared Operation
1
1
except where Dip falls
1
except where Dip falls
2
1
2
Relay remains off
Chapter 3 Page 12 of 42